Texas Administrative Code (Last Updated: March 27,2024) |
TITLE 26. HEALTH AND HUMAN SERVICES |
PART 1. HEALTH AND HUMAN SERVICES COMMISSION |
CHAPTER 553. LICENSING STANDARDS FOR ASSISTED LIVING FACILITIES |
SUBCHAPTER D. FACILITY CONSTRUCTION |
DIVISION 7. EXISTING LARGE TYPE B ASSISTED LIVING FACILITIES |
SECTION 553.141. Construction Requirements for an Existing Large Type B Assisted Living Facility
Latest version.
-
(a) Structurally sound. An existing large Type B assisted living facility must ensure any building is structurally sound regarding actual or expected dead, live, and wind loads according to applicable building codes. (b) Separation of occupancies. An existing large Type B assisted living facility must be separated from other occupancies by a fire barrier having at least a 2-hour fire resistance rating constructed according to the requirements of NFPA 101 and its referenced standards, unless otherwise permitted by paragraphs (1) or (2) of this subsection. (1) An existing large Type B assisted living facility is not required to be separated from a hospital or nursing facility unless the separation is required by NFPA 101 or the standards for licensing the hospital or nursing facility. Beginning August 31, 2021, an existing large Type B assisted living facility must be separated from any new occupancy or new use subject to the Texas Health and Human Services Commission (HHSC) licensing. (2) An existing large Type B assisted living facility is not required to be separated from another occupancy not subject to HHSC licensing standards if the two occupancies are so intermingled that construction of a fire barrier having a 2-hour fire resistance rating is impractical and the following conditions are met. (A) The means of egress, construction, protection, and other safeguards for the entire building must comply with the NFPA 101 requirements for an existing large Type B assisted living facility. (B) HHSC must be given unrestricted and unannounced access at any reasonable time to inspect the other occupancy type for compliance with the NFPA 101 requirements for an existing large Type B assisted living facility. (c) Construction type. An existing large Type B assisted living facility must ensure a building housing the facility meets the requirements of 19.1.6, Minimum Construction Requirements, in NFPA 101, Chapter 19, Existing Health Care Occupancies. (d) Interior finish. An existing Large Type B assisted living facility must ensure interior wall, ceiling and floor finish materials meet the requirements of 19.3.3, Interior Finish, in NFPA 101, Chapter 19, Existing Health Care Occupancies. (e) Vertical openings. An existing large Type B assisted living facility must ensure vertical openings are protected according to the requirements of 19.3.1, Protection of Vertical Openings, in NFPA 101, Chapter 19, Existing Health Care Occupancies. Source Note: The provisions of this §553.141 adopted to be effective August 31, 2021, 46 TexReg 5189